NA2XS(F)2Y V 20 1x150RM/25 M3.0KW #D

Description

Description

Standards

  • Product
    DIN VDE 0276 part 620; IEC 60502-2

Application

Single core MV cable suitable for outdoor and indoor installation, in air, in grounds, in cable ducts.

This product is also part of our Windlink® offer dedicated to wind turbines.

Construction

The single core MV cable is consisted of stranded aluminium conductor, conductor screen of semiconducting compound, insulation of cross-linked polyethylene (XLPE), screen of semiconducting compound, semiconducting tape, screen of copper wires and copper tape, longitudinal water protection, separation tape, PE sheath with increased thickness.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular
Conductor flexibility
Class 2
Lead free
Yes
Halogen free
Yes
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Semi-conducting compound
Material of bedding
Semiconducting tapes
Screen
Copper wire + copper tape
Outer sheath
PE
Longitudinally watertight
Yes
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
150 mm²
Phase Conductor Cross Section
150 mm²
Nominal insulation thickness
5.5 mm
Screen section
25 mm²
Nominal outer sheath thickness
3.0 mm
Nominal outer diameter
38.0 mm
Outer Diameter
38 mm
Approximate weight
1405 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Perm. current rating buried 20°C - trefoil formation
319 A
Perm. current rating in air 30°C - trefoil formation
366 A
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
15 (xD)

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1001047-GRLA
  • Certification Date : 11/11/21
  • AVCP (Assessment and Verification of Constancy of Performance) : System 4
  • Declared performance : Fca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.