AL/XLPE/CWS/PE 6.35/11KV - BS 7870-4.20

Products

AL/XLP/PE 11 3X 70/60 C RD #D #R

Nexans ref. 13004871 - Country ref. 13004871

  • Packaging: Cut to length (m)
  • Conductor flexibility: Stranded class 2
  • Conductor cross-section: 70 mm²
  • Phase Conductor Cross Section: 70 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 48.0 mm

 

AL/XLP/PE 11 3X 70/60 U RD #D #R

Nexans ref. 13004944 - Country ref. 13004944

  • Packaging: Cut to length (m)
  • Conductor flexibility: Solid class 1
  • Conductor cross-section: 70 mm²
  • Phase Conductor Cross Section: 150 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 48.0 mm

 

AL/XLP/PE 11 3X150/60 C RD #D #R

Nexans ref. 13004793 - Country ref. 13004793

  • Packaging: Cut to length (m)
  • Conductor flexibility: Stranded class 2
  • Conductor cross-section: 150 mm²
  • Phase Conductor Cross Section: 150 mm²
  • Nominal outer sheath thickness: 2.9 mm
  • Nominal outer diameter: 59.0 mm

 

AL/XLP/PE 11 3X150/60 U RD #D #R

Nexans ref. 13004945 - Country ref. 13004945

  • Packaging: Cut to length (m)
  • Conductor flexibility: Solid class 1
  • Conductor cross-section: 150 mm²
  • Phase Conductor Cross Section: 150 mm²
  • Nominal outer sheath thickness: 2.9 mm
  • Nominal outer diameter: 59.0 mm

 

AL/XLP/PE 11 3X240/60 C RD #D #R

Nexans ref. 13004821 - Country ref. 13004821

  • Packaging: Cut to length (m)
  • Conductor flexibility: Stranded class 2
  • Conductor cross-section: 240 mm²
  • Phase Conductor Cross Section: 240 mm²
  • Nominal outer sheath thickness: 3.2 mm
  • Nominal outer diameter: 68.0 mm

 

AL/XLP/PE 11 3X240/60 U RD #D #R

Nexans ref. 13004946 - Country ref. 13004946

  • Packaging: Cut to length (m)
  • Conductor flexibility: Solid class 1
  • Conductor cross-section: 240 mm²
  • Phase Conductor Cross Section: 240 mm²
  • Nominal outer sheath thickness: 3.2 mm
  • Nominal outer diameter: 68.0 mm

 

AL/XLP/PE 11 3X300/60 C RD #D #R

Nexans ref. 13004943 - Country ref. 13004943

  • Packaging: Cut to length (m)
  • Conductor flexibility: Stranded class 2
  • Conductor cross-section: 300 mm²
  • Phase Conductor Cross Section: 300 mm²
  • Nominal outer sheath thickness: 3.3 mm
  • Nominal outer diameter: 78.0 mm

 

AL/XLP/PE 11 3X300/60 U RD #D #R

Nexans ref. 13004947 - Country ref. 13004947

  • Packaging: Cut to length (m)
  • Conductor flexibility: Solid class 1
  • Conductor cross-section: 300 mm²
  • Phase Conductor Cross Section: 300 mm²
  • Nominal outer sheath thickness: 3.3 mm
  • Nominal outer diameter: 78.0 mm

 

Description

Description

Standards

  • International
    IEC 60502-2
  • National
    BS 7870-4.20

Electric cable with stranded (class 2) Aluminium conductor, with water protection or solid Aluminium conductor (SAC, conductor screen of semiconducting compound, XLPE insulation, insulation screen of semiconducting compound, three insulated cores are laid-up to created the cable core, collective metallic screen copper wires and copper helix tape, PE outer sheath. 

 

Application

in grounds, outdoors, indoors and in cable ducts 

The cable is suitable for rated voltage 6/10KV (Um=12KV) according to the IEC standards.

 

Note:

other cross section of metallic screen are available on request.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Semi-conducting compound
Screen
Copper wires + copper tape
Outer sheath
PE
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Nominal insulation thickness
3.4 mm
Screen section
60 mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
6.35 / 11 kV

Usage characteristics

Usage characteristics

Flame retardant
No

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close